15KVP - 15k Voltage Probe
This means that connecting this probe to other meters results in an impedance mismatch which results in inaccurate readings.
Therefore our 15KVP probe is only guaranteed to work with PowerSight meters and due to the inherent risk when working with elevated voltages, we will not sell it to a customer who will use it with some other measuring device.
Use of a 15KVP on a device other than a PowerSight meter voids all warranties for the probe and is undertaken by the user at their own risk.
Features
- Connect directly to 3 phase 15KV
- Allows bypassing PTs (Potential Transformers)
- Shepherd’s hook for easy connection to medium voltage (0.75 inch inside diameter)
- Shepherd’s hooks may be unscrewed and replaced by alternative safe attachment method
- All connections are labeled and advisory labels are attached, for review each time the probes are used
- Measure harmonics up to 900 Hz
- For use exclusively with PowerSight® line of Energy Analyzers
Specifications
Voltage Measurement Range: 600 to 15,000 Vrms
Voltage Linearity: +/-1% over measurement range
Frequency Response: Attenuation of 1db from 50 to 900 Hz (i.e. measurements attenuated 11% at 900 Hz, which is 15th harmonic at 60Hz or 18th harmonic at 50Hz).
Probe Dimensions: 16.5 inches long by 1.25 inch diameter. Hook at top has 2 inch outside diameter. Threaded coupling at bottom is 5/8 inch coarse thread.
Shepherd’s Hook Dimensions: connection hook at the top has 0.75 inch inside diameter. It may be replaced with a custom connection item by unscrewing and replacing with a custom accessory with ¼ - 20 threaded male coupling.
Scale: For direct reading of actual voltage, set meter for 60:1 input ratio.